List
- 01.General
- 0101.On
- 0102.Off
- 0103.Toggle
- 0104.Momentary (follow)
- 0105.Execute action set by hardware
- 0106.Up
- 0107.Immediately up
- 0108.Immediately up when initiator opens
- 0109.Immediately up
- 0110.Down
- 0111.Immediately down
- 0112.Immediately down when initiator opens
- 0113.Immediately down
- 0114.Up/down
- 0115.Go to position
- 0116.Go to position when initiator opens
- 0117.Comfort/III mode
- 0118.Day/II mode
- 0119.Night/I mode
- 0120.Safe/standby mode
- 0121.Heating mode
- 0122.Cooling mode
- 0123.Forced Safe mode
- 0124.Forced Safe mode while initiator is closed
- 0125.Forced Safe mode while initiator is open
- 0126.Cancel forced Safe mode
- 0127.Toggle forced Safe mode
- 0128.Lock local control
- 0129.Unlock local control
- 0130.Disable while initiator is closed
- 0131.Disable while initiator is open
- 0132.Force screensaver to off
- 0133.Cancel force screensaver to off
- 0134.Reset absence timer while initiator is closed
- 0135.Monitor status of initiator
- 0136.Comfort/III mode (continuous at long press, temporarily at short press)
- 0137.Day/II mode (continuous at long press, temporarily at short press)
- 0138.Night/I mode (continuous at long press, temporarily at short press)
- 0139.Safe/standby mode (continuous at long press, temporarily at short press)
- 0140.Set to mode 1
- 0141.Set to mode 2
- 0142.Set to mode 3
- 0143.Set to mode 4
- 02.Dimming
- 0201.Dim up/down
- 0202.Dim at long press, toggle at short press
- 0203.Dim at long press, memory or off at short press
- 0204.Dim up
- 0205.Dim up at long press, on at short press
- 0206.Dim up at long press, memory at short press
- 0207.Dim down
- 0208.Dim down at long press, off at short press
- 0209.Dim to set percent
- 0210.Dim to set percent over time
- 0211.Turn on gradually
- 0212.Turn off gradually
- 0213.Slave (following initiator)
- 0214.Atmospheric dimvalue
- 0215.Multi step dimmer
- 03.Dim slowly on / dim slowly off
- 0301.Slow on
- 0302.Slow on when initiator closes, slow off when initiator opens
- 0303.Slow off
- 0304.Slow on/off
- 04.Timer
- 0401.Start timer 1
- 0402.Toggle timer 1
- 0403.Start timer 2
- 0404.Toggle timer 2
- 0405.Start/stop timer
- 0406.Trigger-on-release timer
- 0407.Non-restartable timer
- 0408.Start/stop timer
- 0409.Start/stop timer with slow on/off
- 0410.Restartable timer
- 0411.Restartable timer with slow on/off
- 0412.Restartable timer
- 0413.Non-restartable timer
- 0414.Non-restartable timer with slow on/off
- 0415.Start/stop interval timer
- 0416.Restartable interval timer
- 0417.Non-restartable interval timer
- 05.Delays
- 06.Lock / unlock
- 07.Inhibit
- 0701.Inhibit
- 0702.Inhibit while initiator is closed
- 0703.Inhibit while initiator is open
- 0704.Cancel inhibit
- 0705.Toggle inhibit
- 0706.Inhibit preset up
- 0707.Inhibit but preset up while initiator is closed
- 0708.Inhibit but preset up while initiator is open
- 0709.Cancel inhibit but preset up
- 0710.Toggle inhibit but preset up
- 0711.Inhibit preset down
- 0712.Inhibit but preset down while initiator is closed
- 0713.Inhibit but preset down while initiator is open
- 0714.Cancel inhibit but preset down
- 0715.Toggle inhibit but preset down
- 08.Forced
- 0801.Forced on
- 0802.Forced on while initiator is closed
- 0803.Forced on while initiator is open
- 0804.Cancel forced on
- 0805.Toggle forced on
- 0806.Forced off
- 0807.Forced off while initiator is closed
- 0808.Forced off while initiator is open
- 0809.Cancel forced off
- 0810.Toggle forced off
- 0811.Forced up
- 0812.Forced up while initiator is closed
- 0813.Forced up while initiator is open
- 0814.Cancel forced up
- 0815.Toggle forced up
- 0816.Forced down
- 0817.Forced down while initiator is closed
- 0818.Forced down while initiator is open
- 0819.Cancel forced down
- 0820.Toggle forced down
- 0821.Force to current position
- 0822.Force to current position while initiator is closed
- 0823.Force to current position while initiator is open
- 0824.Cancel force to current position
- 0825.Force/cancel force to current position
- 09.Programs
- 0901.Enable program steps for this channel
- 0902.Disable program steps for this channel
- 0903.Disable program steps for this channel while initiator is closed
- 0904.Disable program steps for this channel while initiator is open
- 0905.Toggle program steps for this channel
- 0906.Select no program
- 0907.Select program 1
- 0908.Select program 2
- 0909.Select program 3
- 0910.Toggle program 1
- 0911.Toggle program 2
- 0912.Toggle program 3
- 0913.Enable alarm/sunrise/sunset
- 0914.Enable alarm/sunrise/sunset while initiator is closed
- 0915.Enable alarm/sunrise/sunset while initiator is open
- 0916.Disable alarm/sunrise/sunset
- 0917.Disable alarm/sunrise/sunset while initiator is closed
- 0918.Disable alarm/sunrise/sunset while initiator is open
- 0919.Toggle alarm/sunrise/sunset
- 10.Clock alarms
- 1001.Enable Clock Alarm 1 related program steps
- 1002.Enable Clock Alarm 1 related program steps while initiator is closed
- 1003.Enable Clock Alarm 1 related program steps while initiator is open
- 1004.Disable Clock Alarm 1 related program steps
- 1005.Disable Clock Alarm 1 related program steps while initiator is closed
- 1006.Disable Clock Alarm 1 related program steps while initiator is open
- 1007.Toggle Clock Alarm 1 related program steps
- 1008.Enable Clock Alarm 2 related program steps
- 1009.Enable Clock Alarm 2 related program steps while initiator is closed
- 1010.Enable Clock Alarm 2 related program steps while initiator is open
- 1011.Disable Clock Alarm 2 related program steps
- 1012.Disable Clock Alarm 2 related program steps while initiator is closed
- 1013.Disable Clock Alarm 2 related program steps while initiator is open
- 1014.Toggle Clock Alarm 2 related program steps
- 1015.Enable Clock Alarm 1 related program steps
- 1016.Enable Clock Alarm 1 related program steps while initiator is closed
- 1017.Enable Clock Alarm 1 related program steps while initiator is open
- 1018.Disable Clock Alarm 1 related program steps
- 1019.Disable Clock Alarm 1 related program steps while initiator is closed
- 1020.Disable Clock Alarm 1 related program steps while initiator is open
- 1021.Toggle Clock Alarm 1 related program steps
- 1022.Enable Clock Alarm 2 related program steps
- 1023.Enable Clock Alarm 2 related program steps while initiator is closed
- 1024.Enable Clock Alarm 2 related program steps while initiator is open
- 1025.Disable Clock Alarm 2 related program steps
- 1026.Disable Clock Alarm 2 related program steps while initiator is closed
- 1027.Disable Clock Alarm 2 related program steps while initiator is open
- 1028.Toggle Clock Alarm 2 related program steps
- 11.Sunrise / Sunset
- 1101.Enable Sunrise related program steps
- 1102.Enable Sunrise related program steps while initiator is closed
- 1103.Enable Sunrise related program steps while initiator is open
- 1104.Disable Sunrise related program steps
- 1105.Disable Sunrise related program steps while initiator is closed
- 1106.Disable Sunrise related program steps while initiator is open
- 1107.Toggle Sunrise related program steps
- 1108.Enable Sunset related program steps
- 1109.Enable Sunset related program steps while initiator is closed
- 1110.Enable Sunset related program steps while initiator is open
- 1111.Disable Sunset related program steps
- 1112.Disable Sunset related program steps while initiator is closed
- 1113.Disable Sunset related program steps while initiator is open
- 1114.Toggle Sunset related program steps
- 1115.Enable sunrise related program steps
- 1116.Enable sunrise related program steps while initiator is closed
- 1117.Enable sunrise related program steps while initiator is open
- 1118.Disable sunrise related program steps
- 1119.Disable sunrise related program steps while initiator is closed
- 1120.Disable sunrise related program steps while initiator is open
- 1121.Toggle sunrise related program steps
- 1122.Enable sunset related program steps
- 1123.Enable sunset related program steps while initiator is closed
- 1124.Enable sunset related program steps while initiator is open
- 1125.Disable sunset related program steps
- 1126.Disable sunset related program steps while initiator is closed
- 1127.Disable sunset related program steps while initiator is open
- 1128.Toggle sunset related program steps
- 12.Disable timer
- 1201.On with timers disabled
- 1202.On with timers disabled at short press
- 1203.On with timers disabled at long press
- 1204.Off with timers disabled
- 1205.Off with timers disabled at short press
- 1206.Off with timers disabled at long press
- 1207.On with timers disabled/off
- 1208.On with timers disabled/off at short press
- 1209.On with timers disabled/off at long press
- 13.Mode selection
- 14.Actions in mode 1
- 1401.Up, only in mode 1
- 1402.Immediately up, only in mode 1
- 1403.Immediately up when initiator opens, only in mode 1
- 1404.Down, only in mode 1
- 1405.Immediately down, only in mode 1
- 1406.Immediately down when initiator opens, only in mode 1
- 1407.Up/down, only in mode 1
- 1408.Go to position, only in mode 1
- 1409.Go to position when initiator opens, only in mode 1
- 15.Actions in mode 2
- 1501.Up, only in mode 2
- 1502.Immediately up, only in mode 2
- 1503.Immediately up when initiator opens, only in mode 2
- 1504.Down, only in mode 2
- 1505.Immediately down, only in mode 2
- 1506.Immediately down when initiator opens, only in mode 2
- 1507.Up/down, only in mode 2
- 1508.Go to position, only in mode 2
- 1509.Go to position when initiator opens, only in mode 2
- 16.Actions in mode 3
- 1601.Up, only in mode 3
- 1602.Immediately up, only in mode 3
- 1603.Immediately up when initiator opens, only in mode 3
- 1604.Down, only in mode 3
- 1605.Immediately down, only in mode 3
- 1606.Immediately down when initiator opens, only in mode 3
- 1607.Up/down, only in mode 3
- 1608.Go to position, only in mode 3
- 1609.Go to position when initiator opens, only in mode 3
01 General
0101. On
Description:
When the initiator closes or is pressed, the subject closes (on).
Diagrams:
Parameters:
None
Feedback behaviour:
LED on when subject is closed (on), blinking while timer is running
Examples:
On button
This action applies to:
0102. Off
0103. Toggle
Description:
Each time the initiator closes or is pressed, the subject toggles (if it was on, it is switched off; if it was off, it is switched on).
Diagrams:
Parameters:
None
Feedback behaviour:
LED on when subject is closed (on), blinking while timer is running
Examples:
On / off button
This action applies to:
0104. Momentary (follow)
Description:
As long as the initiator is open (off, released), the subject is open (off). As long as the initiator is closed (on, pressed), the subject is closed (on).
When several initiators are linked to the same subject using 0104. Momentary (follow) actions, they function as a logical OR: as long as one or more of the initiators is closed (pressed, on), the subject will be closed (on). Only when all initiators are open (off, released), the subject will be open (off).
Caution: this logical OR function will be cancelled if another action (eg. 0102. Off) intervenes.
Diagrams:
Parameters:
None
Feedback behaviour:
LED on when subject is closed (on), blinking while timer is running
Examples:
- Door bell (initiator = push button, subject = bell relay)
- As long as the lights in the toilet are on, a ventilator works (initiator = light relay, subject = ventilator relay)
- Automatically switch off the power supply of a dimmable fixture when the light is off (initiator = dimming channel, subject = relay controlling the power supply).
This action applies to:
0105. Execute action set by hardware
0106. Up
Description:
The initiator is a push button
- short press: the blind goes up, either completely or until a down action is initiated.
- long press: the blind goes up as long as the button is pressed. The motor stops when the button is released.
If the blind was going down, a short or long press will stop the motor.
The initiator is a relay or sensor
The blind goes up when the initiator closes. If the blind was going down, it will stop. If the initiator is not a push button, in most cases the action 0109. Immediately up is more suitable.
Parameters:
None
Feedback behaviour:
LED blinks while the blind goes up, and is constantly lit when completely up
This action applies to:
0107. Immediately up
0108. Immediately up when initiator opens
Description:
When the initiator opens or is released, the blind goes up completely. When a down action is started during the rolling up, the blind will stop.
The motor only starts after the on delay.
Parameters:
- On delay
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
Feedback behaviour:
LED blinks during on delay and while the blind goes up, and is constantly lit when completely up
This action applies to:
0109. Immediately up
Description:
When the initiator closes or is pressed, the blind goes completely up. When a down action is started during the rolling up, the blind will stop.
The motor only starts after the on delay.
Parameters:
- On delay
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
Feedback behaviour:
LED blinks during on delay and while the blind goes up, and is constantly lit when completely up
This action applies to:
0110. Down
Description:
The initiator is a push button
- short press: the blind goes down, either completely or until an up action is initiated.
- long press: the blind goes down as long as the button is pressed. The motor stops when the button is released.
If the blind was going up, a short or long press will stop the motor.
The initiator is a relay or sensor
The blind goes down when the initiator closes. If the blind was going up, it will stop. If the initiator is not a push button, in most cases the action 0113. Immediately down is more suitable.
Parameters:
None
Feedback behaviour:
LED blinks while the blind goes down, and is constantly lit when completely down
This action applies to:
0111. Immediately down
0112. Immediately down when initiator opens
Description:
When the initiator opens or is released, the blind goes completely down. When an up action is started during the rolling down, the blind will stop.
The motor only starts after the on delay.
Parameters:
- On delay
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
Feedback behaviour:
LED blinks during on delay and while the blind goes down, and is constantly lit when completely down
This action applies to:
0113. Immediately down
Description:
When the initiator closes or is pressed, the blind goes completely down. When an up action is started during the rolling down, the blind will stop.
The motor only starts after the on delay .
Parameters:
- On delay
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
Feedback behaviour:
LED blinks during on delay and while the blind goes down, and is constantly lit when completely down
This action applies to:
0114. Up/down
Description:
Single button control for up and down. The direction of the movement changes after each stop.
A short press will roll the blind completely up or down. A long press will roll it up or down as long as the button remains pressed.
If the blind was already moving, a short or long press will stop it.
Parameters:
None
Feedback behaviour:
LED blinks while the blind moves, is off when the blind is completely up and is constantly lit when completely down
This action applies to:
0115. Go to position
Description:
When the initiator closes or is pressed (and after expiration of the on delay), the blind will move to the configured position (adjustable between 0% and 100%).
Parameters:
- On delay
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
- Position
- 0% (compl. up) to 100% (compl. down)
- Default value: 0% (compl. up)
Feedback behaviour:
LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position
This action applies to:
0116. Go to position when initiator opens
Description:
When the initiator opens or is released (and after expiration of the on delay), the blind will move to the configured position (adjustable between 0% and 100%).
Parameters:
- On delay
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
- Position
- 0% (compl. up) to 100% (compl. down)
- Default value: 0% (compl. up)
Feedback behaviour:
LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position
This action applies to:
0117. Comfort/III mode
Description:
Switch the thermostat to comfort mode (when heating) or position III (when cooling).
The duration option Default sleep time refers to the sleep time configured in the module configuration settings.
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
- Duration at long press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: No Action
Feedback behaviour:
LED on when thermostat is in corresponding mode (slow blinking if timer is running)
This action applies to:
0118. Day/II mode
Description:
Switch the thermostat to day mode (when heating) or position II (when cooling).
The duration option Default sleep time refers to the sleep time configured in the module configuration settings.
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
- Duration at long press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: No Action
Feedback behaviour:
LED on when thermostat is in corresponding mode (slow blinking if timer is running)
This action applies to:
0119. Night/I mode
Description:
Switch the thermostat to night mode (when heating) or position I (when cooling).
The duration option Default sleep time refers to the sleep time configured in the module configuration settings.
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
- Duration at long press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: No Action
Feedback behaviour:
LED on when thermostat is in corresponding mode (slow blinking if timer is running)
This action applies to:
0120. Safe/standby mode
Description:
Switch the thermostat to safe mode (when heating) or standby position (when cooling).
The duration option Default sleep time refers to the sleep time configured in the module configuration settings.
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
- Duration at long press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: No Action
Feedback behaviour:
LED on when thermostat is in corresponding mode (slow blinking if timer is running)
This action applies to:
0121. Heating mode
0122. Cooling mode
0123. Forced Safe mode
Description:
Switch the thermostat to forced safe mode (when heating) or forced standby mode (when cooling). The thermostat will remain in forced safe (or standby) mode until cancelled by action 0126. Cancel forced Safe mode or 0127. Toggle forced Safe mode.
When forced mode is cancelled, the thermostat returns to the last mode before forcing.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED on when thermostat is in forced safe mode
This action applies to:
0124. Forced Safe mode while initiator is closed
Description:
As long as the initiator is closed (on, pressed), the thermostat is set to forced safe mode (when heating) or forced standby mode (when cooling). The thermostat will remain in forced safe (or standby) mode until the initiator opens (switches off) again.
Parameters:
None
Feedback behaviour:
LED on when thermostat is in forced safe mode
This action applies to:
0125. Forced Safe mode while initiator is open
Description:
As long as the initiator is open (off, released), the thermostat is set to forced safe mode (when heating) or forced standby mode (when cooling). The thermostat will remain in forced safe (or standby) mode until the initiator closes (switches on) again.
Parameters:
None
Feedback behaviour:
LED on when thermostat is in forced safe mode
This action applies to:
0126. Cancel forced Safe mode
0127. Toggle forced Safe mode
Description:
This action combines 0123. Forced Safe mode and 0126. Cancel forced Safe mode. If the thermostat was in forced mode when the initiator closes, action 0126. Cancel forced Safe mode will be executed. If the thermostat was not in forced mode when the initiator closes, action 0123. Forced Safe mode will be executed.
The duration parameter only applies to the forcing, not to the cancelling.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED on when thermostat is in forced safe mode (slow blinking if timer is running)
This action applies to:
0128. Lock local control
Description:
Locks the local control button on the module, so users can no longer control the thermostat by pressing the button on the module. See also 0129. Unlock local control.
Parameters:
None
Feedback behaviour:
LED on when local control is locked
This action applies to:
0129. Unlock local control
Description:
Unlocks the local control button on the module, so users can control the thermostat again by pressing the button on the module. See also 0128. Lock local control.
Parameters:
None
Feedback behaviour:
LED on when local control is unlocked
This action applies to:
0130. Disable while initiator is closed
Description:
As long as the initiator is closed (on, pressed), the thermostat is inhibited and set to safe mode (when heating) or standby position (when cooling).
Parameters:
None
Feedback behaviour:
LED on when thermostat is inhibited and in safe mode
Examples:
A (normally open) window contact turns off the heating when the window is open.
This action applies to:
0131. Disable while initiator is open
Description:
As long as the initiator is open (off, released), the thermostat is inhibited and set to safe mode (when heating) or standby position (when cooling).
Parameters:
None
Feedback behaviour:
LED on when thermostat is inhibited and in safe mode
Examples:
A (normally closed) window contact turns off the heating when the window is open.
This action applies to:
0132. Force screensaver to off
Description:
Override screensaver settings of the subject module and force its screensaver to off (instead of dimmed).
Parameters:
None
Feedback behaviour:
LED on when screensaver mode is forced to off
Examples:
Eg. for a bedroom, to avoid unwanted illumination by the oled during the night.
This action applies to:
0133. Cancel force screensaver to off
Description:
Cancel action 0132. Force screensaver to off and return the screensaver mode to the one defined in the module configuration settings.
Parameters:
None
Feedback behaviour:
LED on when screensaver mode is not forced to off
This action applies to:
0134. Reset absence timer while initiator is closed
0135. Monitor status of initiator
Description:
Make the subject's feedback LED display the status of the initiator. For this action to work, the LED feedback of the subject channel has to be set to Monitoring (in the module configuration settings).
Parameters:
None
Examples:
Example: A push button switches the light in a room. Instead of displaying the status of the light in the room, we want the push button's LED to display the status of another light (eg. the driveway light). In order to do so change the LED feedback setting of the push button to Monitoring, and create an action 0135. Monitor status of initiator with as initiator the driveway light relay, and as subject the push button.
This action applies to:
0136. Comfort/III mode (continuous at long press, temporarily at short press)
Description:
Set the thermostat to comfort mode (when heating) or position III (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)
Parameters:
None
Feedback behaviour:
LED on when thermostat is in corresponding mode
This action applies to:
0137. Day/II mode (continuous at long press, temporarily at short press)
Description:
Set the thermostat to day mode (when heating) or position II (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)
Parameters:
None
Feedback behaviour:
LED on when thermostat is in corresponding mode
This action applies to:
0138. Night/I mode (continuous at long press, temporarily at short press)
Description:
Set the thermostat to night mode (when heating) or position I (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)
Parameters:
None
Feedback behaviour:
LED on when thermostat is in corresponding mode
This action applies to:
0139. Safe/standby mode (continuous at long press, temporarily at short press)
Description:
Set the thermostat to safe mode (when heating) or standby position (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)
Parameters:
None
Feedback behaviour:
LED on when thermostat is in corresponding mode
This action applies to:
0140. Set to mode 1
Description:
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
Examples:
This action applies to:
0141. Set to mode 2
Description:
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
Examples:
This action applies to:
0142. Set to mode 3
Description:
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
Examples:
This action applies to:
0143. Set to mode 4
Description:
Parameters:
- Duration at short press
- No action
- Until next program step
- Default sleep time
- 15 min to 45 days
- Ignore all program steps
- Default value: Until next program step
Examples:
This action applies to:
02 Dimming
0201. Dim up/down
Description:
Single button control, combining 0204. Dim up and 0207. Dim down. Each time the initiator closes or is pressed, the dimming direction will be opposite from the last one the subject channel has used.
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
Diagrams:
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0202. Dim at long press, toggle at short press
Description:
- long press = 0201. Dim up/down
- short press = 0103. Toggle
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0203. Dim at long press, memory or off at short press
Description:
- long press = 0201. Dim up/down
- short press = if current dimming value is 0%, go to previous value; if current dimming value is different from 0%, turn off
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0204. Dim up
Description:
As long as the initiator is closed (on, pressed), the dimmer keeps dimming up (the dim value increases). For standard operation (dim button) the duration is set to continuous.
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
See also 0207. Dim down.
Diagrams:
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0205. Dim up at long press, on at short press
Description:
- long press = 0204. Dim up
- short press = 0101. On
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0206. Dim up at long press, memory at short press
Description:
- long press = 0204. Dim up
- short press = if current dimming value is different from 0%: no action; if current dimming value is 0%, go to previous value
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0207. Dim down
Description:
As long as the initiator is closed (on, pressed), the dimmer keeps dimming down (the dim value decreases). For standard operation (dim button) the duration is set to continuous.
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released.
See also 0204. Dim up.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0208. Dim down at long press, off at short press
Description:
- long press = 0207. Dim down
- short press = 0102. Off
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0209. Dim to set percent
0210. Dim to set percent over time
Parameters:
- Dim up/down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
- Dim percentage
- 0 to 100%
- Default value: 50%
This action applies to:
0213. Slave (following initiator)
Description:
This action is used for master/slave dimming. Master/slave dimming uses the initiator dimming channel as the master. When dimming the master channel up or down, the slave will follow. But when dimming the slave up or down, the master channel will not follow.
The master must be initiator of this action, and the slave subject.
Don't forget to set the master dimming channel as master in the configuration settings of the dimmer module.
Parameters:
None
This action applies to:
0214. Atmospheric dimvalue
Description:
When the initiator closes or is pressed, the light dims to the set dimming value. This value can be set in percentages ranging from 0% (completely off) to 100% (completely on) in steps of 1%.
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%. The timer is restartable.
The dim up / down duration defines how long it will take to dim gradually from the current percentage to the target percentage.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
- Dim up/down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
- Dim percentage
- 0 to 100%
- Default value: 50%
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
This action applies to:
0215. Multi step dimmer
Description:
A list of dimming values is entered in the dimmer's configuration settings. Every time the initiator closes, the dimmer will go to the next dimming value (similar to consecutively activating dim percentages with a single button, see action 0214. Atmospheric dimvalue).
By entering only two dim values in the list (eg. 0% and 65%), this action can be used as a dim toggle.
If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
- Dim up/down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
Feedback behaviour:
LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)
Examples:
With each press on a button, the dimmer cycles through the dimming values 0%, 25%, 50%, 75% and then 0% etc. (the number of steps and their values can be freely configured).
This action applies to:
03 Dim slowly on / dim slowly off
0301. Slow on
Description:
When the initiator closes or is pressed, the dimming channel goes slowly to 100%.
Parameters:
- Dim up duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
Feedback behaviour:
LED off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when dimming value different from 0% is reached
Examples:
Slow on.
This action applies to:
0302. Slow on when initiator closes, slow off when initiator opens
Description:
When the initiator closes or is pressed, the dimming channel will go slowly to 100% (see action 0301. Slow on). It will then remain on during duration ('continuous' = until it is switched off). When the initiator is released or opened, or when the timer expires, the dimming channel will go off slowly (see action 0303. Slow off).
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: Continuous
- Dim up duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
- Dim down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
Feedback behaviour:
LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)
Examples:
Slow on, remain on during a certain time, then slow off.
This action applies to:
0303. Slow off
0304. Slow on/off
Description:
When the initiator closes or is pressed, and the dimvalue = 0%, action 0301. Slow on is executed.
When the initiator closes or is pressed, and the dimvalue is different from 0%, action 0303. Slow off is executed.
Parameters:
- Dim down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Dim up duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
Feedback behaviour:
LED always off
This action applies to:
04 Timer
0405. Start/stop timer
Description:
When the initiator closes or is pressed, the subject closes and a timer starts to run. The subject opens when the timer expires.
If the initiator is closed while the timer is running, the timer stops (and is reset to zero) and the subject opens.
A short press can start another timer than a long press, provided the initiator is a push button.
Diagrams:
Parameters:
- Duration at short press
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Duration at long press
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
Feedback behaviour:
LED on when subject is on, blinks while timer is running (normal blinking for short press, slow blinking for long press)
This action applies to:
0406. Trigger-on-release timer
Description:
When the initiator opens or is released, the subject closes and a timer starts to run. The subject opens when the timer expires. If the initiator is opened while the timer is running, the timer restarts.
Diagrams:
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
Feedback behaviour:
LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)
This action applies to:
0407. Non-restartable timer
Description:
When the initiator closes or is pressed, the subject closes and a timer starts to run. The subject opens when the timer expires. The timer cannot be restarted: closing the initiator while the timer is running has no effect.
Diagrams:
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
Feedback behaviour:
LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)
This action applies to:
0408. Start/stop timer
Description:
Similar to 0405. Start/stop timer, but for dimmer channels.
When the initiator closes or is pressed, the subject is turned on (100%), and then turned off (0%) when the timer expires. If the initiator is closed (pressed) while the timer is running, the timer is stopped (and reset to 0) and the subject is turned off (0%).
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 10s
Feedback behaviour:
LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)
This action applies to:
0409. Start/stop timer with slow on/off
Description:
Similar to action 0408. Start/stop timer with adjustable dimming-up and dimming-down durations (see actions 0301. Slow on and 0303. Slow off).
Parameters:
- Dim down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Dim up duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 10s
Feedback behaviour:
LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)
This action applies to:
0410. Restartable timer
Description:
Similar to 0412. Restartable timer, but for dimmer channels.
When the initiator closes or is pressed, the subject is turned on (100%), and then turned off (0%) when the timer expires. If the initiator is closed (pressed) while the timer is running, the timer is restarted (similar to action 0412. Restartable timer).
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 10s
Feedback behaviour:
LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)
This action applies to:
0411. Restartable timer with slow on/off
Description:
Similar to action 0410. Restartable timer with adjustable dimming-up and dimming-down times (see actions 0301. Slow on and 0303. Slow off).
Parameters:
- Dim down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Dim up duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 10s
Feedback behaviour:
LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)
This action applies to:
0412. Restartable timer
Description:
When the initiator closes or is pressed, the subject closes and a timer starts to run. The subject opens when the timer expires. The timer can be restarted by closing the initiator while the timer is running.
A short press can start another timer than a long press, provided the initiator is a push button.
Diagrams:
Parameters:
- Duration at short press
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Duration at long press
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 0s (none)
Feedback behaviour:
LED on when subject is on, blinks while timer is running (normal blinking for short press, slow blinking for long press)
This action applies to:
0413. Non-restartable timer
Description:
Similar to 0407. Non-restartable timer, but for dimmer channels.
When the initiator closes or is pressed, the subject is turned on (100%) and a timer starts to run. The subject is turned off (0%) when the timer expires. The timer cannot be restarted: closing the initiator while the timer is running has no effect.
Parameters:
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 10s
Feedback behaviour:
LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)
This action applies to:
0414. Non-restartable timer with slow on/off
Description:
Similar to action 0413. Non-restartable timer with adjustable dimming-up and dimming-down times (see actions 0301. Slow on and 0303. Slow off).
Parameters:
- Dim down duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Dim up duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 5s
- Duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 10s
Feedback behaviour:
LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)
This action applies to:
0415. Start/stop interval timer
Description:
When the initiator closes or is pressed, an interval timer starts to run on the subject (intermittently on and off).
If the initiator is closed while the timer is running, the timer stops (and is reset to zero) and the subject opens.
An interval timer always starts with a pulse, never with a pause.
Diagrams:
Parameters:
- Total duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 10s
- Pulse duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 1s
- Pause duration
- 0s (none)
- 1s to 3 days
- Continuous
- Default value: 1s
Feedback behaviour:
LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)
This action applies to:
0416. Restartable interval timer
Description:
When the initiator closes or is pressed, an interval timer starts to run on the subject (intermittently on and off).
The timer can be restarted by closing the initiator while the timer is running.
An interval timer always starts with a pulse, never with a pause.